E6581301
A-22
1
2.5kHz 4kHz
8kHz 12kHz 16kHz
Carrier frequency (
EH
)
200V 18.5~45kW (See lines shown in - - - for 22kW)
400V 22~75kW
100%
90%
80%
70%
60%
50%
Output current
40°C: (a)
When the upper protection cover is removed under
condition (a)
(b)
50°C: (a)
When the upper protection cover is removed under
condition (a)
(b)
60°C: (a)
When the upper protection cover is removed under
condition (a)
(b)
mbient temperature: Permanently-installed inverters
400V 90~110kW
2.5kHz 3kHz 4kHz 5kHz 6kHz 7kHz 8kHz
Carrier frequency (
EH
)
100%
90%
80%
70%
60%
50%
40%
output current
mbient temperature: Permanently-installed inverters
50°C: (a)
(b)
60°C: (a)
(b)
400V 132kW
or more
2.5kHz 3kHz 4kHz 5kHz 6kHz 7kHz 8kHz
Carrier frequency (
EH
)
100%
90%
80%
70%
60%
50%
40%
output current
mbient temperature: Permanently-installed inverters
50°C: (a)
(b)
60°C: (a)
(b)
40°C: (a)
(b)
200V 55kW
or more
2.5kHz 3kHz 4kHz 5kHz 6kHz 7kHz 8kHz
Carrier frequency (
EH
)
100%
90%
80%
70%
60%
50%
40%
output current
mbient temperature: Permanently-installed inverters
40°C: (a)
(b)
50°C: (a)
(b)
60°C: (a)
(b)
+ The rated current indicated on the nameplate of a 15kW inverter or smaller is the current that flows at 4kHz. If the
carrier frequency is set at 12kHz by default, therefore, the rated current needs to be decreased.
⇒ For more details, refer to Section 12.
When H=, however, the carrier frequency decreases automatically with increase in current to secure the
rated current for frequencies below 4kHz.
+Random control is exercised when the motor is operated in a low-frequency range where it produces annoying
magnetic noise.
+ If the carrier frequency control mode selection parameter (H) is set to or , the output voltage may drop.
The carrier frequency (EH) should be set below 4kHz.