K-15
E6581301
11
[16] PID control [2/2]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Reference
H 0363 Integral (I) gain 0.01~100.0 0.01/0.01 0.10 Enabled / - ●● *1
H 0364 PID deviation upper limit NN~WN Hz 0.1/0.01 *2 Enabled / - ●● *1
H 0365 PID deviation lower limit NN~WN Hz 0.1/0.01 *2 Enabled / - ●● *1
H 0366 Differential (D) gain 0.00~2.55 0.01/0.01 0.00 Enabled / - ●● *1
*1: For details, refer to Instruction Manual (E6581329) specified in Section 6.41. *2: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
[17] Speed feedback/positioning control
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Reference
H 0367 Process upper limit NN~WN Hz 0.1/0.01 *4 Enabled -/ -/ -- *1
H 0368 Process lower limit NN~WN Hz 0.1/0.01 NN Enabled -/ -/ -- *1
H 0369 PID control waiting time 0~2400 sec. 1/1 0 Enabled -/ -/ -- *1
H 0370 PID output upper limit NN~WN Hz 0.1/0.01 *4 Enabled - - - - *1
H 0371 PID output lower limit NN~WN Hz 0.1/0.01 NN Enabled - - - - *1
H 0372
Process increasing rate (speed type
PID control)
0.1~600.0 0.1/0.1 10.0 Enabled - - - - *1
H 0373
Process decreasing rate (speed
type PID control)
0.1~600.0 0.1/0.1 10.0 Enabled - - - - *1
H 0375 Number of PG input pulses 12~9999 1/1 500 Disabled / -/ -- *2
H 0376
Selection of number of PG input
phases
1:Single-phase input
2:Two-phase input
1/1 2 Disabled / ---*2
H 0377 PG disconnection detection
0:Deselect
1:Select (with filter)
2:Select
(
Detection of momentar
y
power failure
)
1/1 0 Disabled / ---*2
H 0378
Number of RP terminal input
pulses
12~9999 1/1 500 Disabled /●●/ -- *3
H 0381
Simple positioning completion
range
1~4000 1/1 100 Enabled / - ●● *2
*1: For details, refer to Instruction Manual (E6581329) specified in Section 6.41. *2: For details, refer to Instruction Manual (E6581319) specified in Section 6.41.
*3: For details, refer to Instruction Manual (E6581341) specified in Section 6.41. *4: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
[18] Motor constant [1/2]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Constan
t
Reference
H 0400 Auto-tuning 1
0:No auto-tuning
1:Initialize motor constant (0 after execution)
2:Continue operation continued after auto-tuning (0
after execution)
3:Auto-tuning by input terminal signal
4:Motor constant auto calculation (0 after
execution)
1/1 0 Disabled /●●/ - - 6. 22
Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Sensorless vector/vector with sensor (:Effective, -:Ineffective)