K-9
E6581301
11
[6] Speed/torque reference gain/bias setup [2/2]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Reference
H 0212 RR/S4 input point 2 setting 0~100% 1/1 100 Enabled /●●/●●7. 3. 1
CXH 0213 RR/S4 input point 2 frequenc
y
0.0~HJ Hz 0.1/0.01 *4 Enabled / - 5. 11
H 0214 RR/S4 input point 1 rate 0~250% (for torque control etc.) 1/0.01 0 Enabled /●●/ -- *1
H 0215 RR/S4 input point 2 rate 0~250% (for torque control etc.) 1/0.01 100 Enabled /●●/ -- *1
H 0216 RX input point 1 setting -100~100% 1/1 0 Enabled /●●/●●7. 3. 3
H 0217 RX input point 1 frequency 0.0~HJ Hz 0.1/0.01 0.0 Enabled / - ●●7. 3. 3
H 0218 RX input point 2 setting -100~100% 1/1 100 Enabled /●●/●●7. 3. 3
H 0219 RX input point 2 frequency 0.0~HJ Hz 0.1/0.01 *4 Enabled / - ●●7. 3. 3
H 0220 RX input point 1 rate -250~250% (for torque control etc.) 1/0.01 0 Enabled /●●/ -- *1
H 0221 RX input point 2 rate -250~250% (for torque control etc.) 1/0.01 100 Enabled /●●/ -- *1
H 0222 AI1 input point 1 setting -100~100% 1/1 0 Enabled /●●/●● *2
H 0223 AI1 input point 1 frequency 0.0~HJ Hz 0.1/0.01 0.0 Enabled / - ●● *2
H 0224 AI1 input point 2 setting -100-100% 1/1 100 Enabled /●●/●● *2
H 0225 AI1 input point 2 frequency 0.0~HJ Hz 0.1/0.01 *4 Enabled / - ●● *2
H 0226 AI1 input point 1 rate -250~250% (for torque control etc.) 1/0.01 0 Enabled /●●/●● *2
H 0227 AI1 input point 2 rate -250~250% (for torque control etc.)
1/
0.01 100 Enabled /●●/●● *2
H 0228 AI2 input point 1 setting 0~100% 1/1 0 Enabled /●●/●● *2
H 0229 AI2 input point 1 frequency 0.0~HJ Hz 0.1/0.01 0.0 Enabled / - ●● *2
H 0230 AI2 input point 2 setting 0~100% 1/1 100 Enabled /●●/●● *2
H 0231 AI2 input point 2 frequency 0.0~HJ Hz 0.1/0.01 *4 Enabled / - ●● *2
H 0234
RP/hi
g
h speed pulse input point
1 setting
0~100% 1/1 0 Enabled / - ●● *3
H 0235
RP/hi
g
h speed pulse input point
1 frequency
0.0~HJ Hz 0.1/0.01 0.0 Enabled / - ●● *3
H 0236
RP/hi
g
h speed pulse input point
2 setting
0~100% 1/1 100 Enabled / - ●● *3
H 0237
RP/hi
g
h speed pulse input point
2 frequency
0.0~HJ Hz 0.1/0.01 *4 Enabled / - ●● *3
This parameter moves to a fundamental parameter.
*1: For details, refer to Instruction Manual (E6581331) specified in Section 6.41.
*2: For details, refer to Instruction Manual (E6581341) specified in Section 6.41.
*3: ⇒⇒ For details, refer to Instruction Manual (E6581319) specified in Section 6.41.
*4: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
Sensorless vector/vector with sensor (:Effective, -:Ineffective)