6.14 Trip-less intensification
6.14.1 Retry function
H : Retry selection (selecting the no. of times)
Warning
Mandatory
• Stand clear of motors and equipment.
The motor and equipment stop when the alarm is given, selection of the retry function will restart them
suddenly after the specified time has elapsed. This could result in unexpected injury.
• Take measures for safety, e.g. attach a cover to the motor, to prevent accidents if the motor suddenly
restarts.
• Function
This parameter resets the inverter automatically when the inverter gives an alarm. During the retry mode,
the motor speed search function operated automatically as required and thus allows smooth motor
restarting.
[Parameter setting]
Title Function Adjustment range Default setting
H Retry selection (selecting the no. of times) : Deselect, ~ times
The likely causes of tripping and the corresponding retry processes are listed below.
Cause of tripping Retry process Canceling conditions
Momentary power failure
Overcurrent
Overvoltage
Overload
Up to 10 times in succession
1st retry : About 1 sec after tripping
2nd retry : About 2 sec after tripping
3rd retry : About 3 sec after tripping
...
10th retry : About 10 sec. after tripping
The retry function will be canceled at once
if tripping is caused by an unusual event
other than momentary power failure,
overcurrent, overvoltage or overload.
This function will also be canceled if a retry
is not successful within the specified
number of times.
Trips covered by the retry function
E, , : Overcurrent
ER, R, R : Overcurrent in DC section or
overheating of devices
R, , : Overvoltage
N: Inverter overload
N: Motor overload
NT: Braking resistor
overload
J : Overheat
UQWV: PM motor step-out
+The retry function is disabled in the following unusual events:
EC, , : Arm overcurrent at start-up
GRJ : Input phase failure
GRJ : Output phase failure
EN : Loaded side overcurrent at start time
J : External thermal error
WE : Low current
WR : Voltage drop in main circuit
V : Overtorque
GH, GH : Ground fault
G : Emergency stop
GGR, , : EEPROM error
GTT : Main RAM error
GTT : Main ROM error
GTT : CPU trip
GTT : Interruption of operation command from
external control device
GTT : Gate array fault
GTT : Output current detector error
GTT : Optional unit error
G~
• Others (Other than trips covered by the retry function)
+Protective operation detection relay signals (FLA, FLB, FLC terminal signals) are not sent during use of the retry
function. (factory default setting)
+A virtual cooling time is provided for overload tripping (QN, QN, QNT).
See Section 13.2 for the virtual cooling time.
In this case, the retry function operates after the virtual cooling time and retry time.
+In the event of overvoltage tripping (QR~QR), re-tripping may result unless the DC voltage decreases below a
predetermined level.
+In the event of overheating-caused tripping (QJ), re-tripping may result unless the internal temperature decreases
below a predetermined level, since the internal temperature detection function of the inverter works.