K-2
E6581301
11
1. Basic parameter [2/4]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Reference
RV 0015 V/f control mode selection
0:Constant torque characteristics
1:Voltage decrease curve
2:Automatic torque boost
3:Sensorless vector control 1 (speed)
4:Sensorless vector control 2 (speed/torque)
5:V/f 5-point setting
6:PM control
7:PG feedback vector control 1 (speed)
8:PG feedback vector control 2 (speed/torque)
1/1 0 Disabled
-/-
-/-
/-
/-
/-
-/-
-/-
-/
-/
-/-
-/-
-/-
-/-
/-
-/-
-/-
-/-
-/
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5. 6
XD 0016 Manual torque boost 1 0.0~30.0% 0.1/0.1 *1 Enabled - - ●● 5. 7
XN 0014 Base frequency 1 25.0~500.0Hz 0.1/0.01 *3 Disabled /●●/●●5. 8
XNX 0409 Base frequenc
y
volta
g
e 1
200V class:50~330V
400V class:50~660V
1/0.1 *1 Disabled /●●/●●5. 8
HJ 0011 Maximum frequency 30.0~500.0Hz 0.1/0.01 80.0 Disabled /●●/●●5. 9
WN 0012 Upper limit frequency 0.0~HJ Hz 0.1/0.01 *3 Enabled / - ●●5. 10
NN 0013 Lower limit frequency 0.0~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 10
CEE 0009 Acceleration time 1 0.1~6000 sec. 0.1/0.1 *2 *1 Enabled / - ●● 5. 2
FGE 0010 Deceleration time 1 0.1~6000 sec. 0.1/0.1 *2 *1 Enabled / - ●● 5. 2
CXH 0213
RR/S4 input point 2
frequency
0.0~HJ Hz 0.1/0.01 *3 Enabled / - ●● 5. 11
CKH 0204 VI/II input point 2 frequenc
y
0.0~HJ Hz 0.1/0.01 *3 Enabled / - ●● 5. 11
UT 0018
Preset speed operation
frequency 1
NN~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 12
UT 0019
Preset speed operation
frequency 2
NN~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 12
UT 0020
Preset speed operation
frequency 3
NN~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 12
UT 0021
Preset speed operation
frequency 4
NN~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 12
UT 0022
Preset speed operation
frequency 5
NN~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 12
UT 0023
Preset speed operation
frequency 6
NN~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 12
UT 0024
Preset speed operation
frequency 7
NN~WN Hz 0.1/0.01 0.0 Enabled / - ●●5. 12
HT 0008
Forward run/reverse run
selection (operation panel
operation)
0:Forward run
1:Reverse run
2:Forward run
(
Forward/reverse switchable on operation
panel)
3:Reverse run
(
Forward/reverse switchable on operation
panel)
1/1 0 Enabled /●●/●●5. 13
*1: Default values vary depending on the capacity. See the table of K-46.
*2: Changing the parameter VR enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).
*3: Inverter with a model number ending with -WN: 60.0 -WP: 50.0
Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Vista de pagina 239