[10] Jump frequency
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
unit
Panel/Communi
cation)
Default
settin
Write durin
runnin
Speed
control
Torq ue
control
PM
control
V/f Reference
H 0270 Jump frequency 1 0.0~HJ Hz 0.1/0.01 0.0 Enabled ●/● - ●●6. 12
H 0271 Jump step 1 0.0~30.0Hz 0.1/0.01 0.0 Enabled ●/● - ●●6. 12
H 0272 Jump frequency 2 0.0~HJ Hz 0.1/0.01 0.0 Enabled ●/● - ●●6. 12
H 0273 Jump step 2 0.0~30.0Hz 0.1/0.01 0.0 Enabled ●/● - ●●6. 12
H 0274 Jump frequency 3 0.0~HJ Hz 0.1/0.01 0.0 Enabled ●/● - ●●6. 12
H 0275 Jump step 3 0.0~30.0Hz 0.1/0.01 0.0 Enabled ●/● - ●●6. 12
[11] Preset speed operation frequency (8~15)
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
unit
Panel/Communi
cation)
Default
settin
Write durin
runnin
Speed
control
Torq ue
control
PM
control
V/f Reference
H 0287
Preset speed operation
frequency 8
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
H 0288
Preset speed operation
frequency 9
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
H 0289
Preset speed operation
frequency 10
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
H 0290
Preset speed operation
frequency 11
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
H 0291
Preset speed operation
frequency 12
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
H 0292
Preset speed operation
frequency 13
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
H 0293
Preset speed operation
frequency 14
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
H 0294
Preset speed operation
frequency 15
Forced operation frequenc
NN~WN Hz 0.1/0.01 0.0 Enabled ●/● - ●●5. 12
[12] Tripless intensification setup [1/2]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
unit
Panel/Communi
cation)
Default
settin
Write durin
runnin
Speed
control
Torq ue
control
PM
control
V/f Reference
EH 0300 PWM carrier frequency 1.0~16.0kHz (1.0~8.0kHz) *1 0.1/0.1 *2 Enabled ●/● ●/● ● ● 5. 17
WXU 0301 Auto-restart control selection
0:Deselect, 1:At auto-restart
2:ST ON/OFF switching, 3:1+2, 4:Starting
1/1 0 Disabled ●/● ●/● ● ● 5. 18.1
WXE 0302
Regenerative power ride-
through control
0:Deselect
1:Power ride-through
2:Deceleration stop during power failure
3:Synchronized deceleration/acceleration
s
nchronized acceleration/deceleration si
nal
4:Synchronized deceleration/acceleration
(synchronized acceleration/deceleration
signal+power failure)
1/1 0 Disabled ●/● -/- ● ● 5. 18. 2
This parameter moves to a fundamental parameter. *1: For 200V-55/75kW models and 400V-90kW to 400V-280kW models, the carrier frequency is between 1.0 and 8.0kHz inclusive.
*2: Default values vary depending on the capacity. ⇒ See the table of K-46.
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Sensorless vector/vector with sensor (●:Effective, -:Ineffective)