[24] Protection functions [3/3]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Constan
t
Reference
H 0637 PTC1 thermal selection
0:Deselect
1:Select
1/1 0 Disabled /●●/●● *1
H 0638 PTC2 thermal selection
0:Deselect
1:Select
1/1 0 Disabled /●●/●● *1
H 0639
Brakin
g
resistance overload time
(10 times of rated torque)
0.1~600.0 sec. 0.1/0.1 5.0 Disabled /●●/●●5. 19
H 0640
Step-out detection current level
(for PM motors)
10~150 1/1 100 Disabled - - - - 6. 29
H 0641
Step-out detection time (for PM
motors)
0.0:Not detect
0.1~25.0
0.1/0.1 0.0 Disabled - - - - 6. 29
*1: For details, refer to Instruction Manual (E6581339) specified in Section 6.41.
[25] Override
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Constan
t
Reference
H 0660 Override addition input selection
0:Disabled
1:VI/II (voltage/current input)
2:RR/S4 (potentiometer/voltage input)
3:RX (voltage input)
4:Operation panel input enabled (including
LED/LCD option input)
5:2-wire RS485 input enabled
6:4-wire RS485 input enabled
7:Communications option input enabled
8:Optional AI1 (differential current input)
9:Optional AI2 (voltage/current input)
10:UP/DOWN frequency
11:Optional RP pulse input
12:Optional high-speed pulse input
13:Optional binary/BCD input
1/1 0 Enabled / - ●●6. 34
H 0661
Override multiplication input
selection
0:Disabled, 1:VI/II, 2:RR
/
S4, 3:RX, 4:H,
5:Optional AI1
1/1 0 Enabled / - ●●6. 34
H 0669
Logic output/pulse output
selection (OUT1)
0:Logic output
1:Pulse output
1/1 0 Disabled /●●/●●6. 35. 1
COUN 0670 AM terminal meter selection 0~64 *1 1/1 2 Enabled / / 5. 16
This parameter moves to a fundamental parameter.
*1: For the adjustment range, see the table on page K-39.
Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Sensorless vector/vector with sensor (:Effective, -:Ineffective)