K-25
E6581301
11
[26] Meter output
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Constan
t
Reference
CO 0671 AM terminal meter ad
j
ustment - 1/1 - Enabled / / 5. 16
H 0672 MON1 terminal meter selection 0~64 *1 1/1 4 Enabled /●●/●● *2
H 0673
MON1 terminal meter
adjustment
- 1/1 - Enabled /●●/●● *2
H 0674 MON2 terminal meter selection 0~64 *1 1/1 5 Enabled /●●/●● *2
H 0675
MON2 terminal meter
adjustment
- 1/1 - Enabled /●●/●● *2
H 0676 Pulse output function selection 0~49 *1 1/1 0 Enabled /●●/●●6. 35. 1
H 0677 Selection of number of pulses 1.00~43.20kHz 0.01/0.01 3.84 Enabled /●●/●●6. 35. 1
H 0678 Constant at the time of filterin
g
4msec, 8msec~100msec 1/1 64 Disabled /●●/●●6. 35. 1
H 0681
FM voltage/current output
switching
0:Voltage 0~10V output
1:Current 0~20mA output
1/1 0 Disabled /●●/●●6. 35. 3
H 0682
FM output gradient
characteristic
0:Negative gradient (descending)
1:Positive gradient (ascending)
1/1 1 Enabled /●●/●●6. 35. 3
H 0683 FM bias adjustment -10.0~100.0% 0.1/0.1 0.0 Enabled /●●/●●6. 35. 3
H 0684 FM output filter
0:No filter
1:Filter approx. 10ms
2:Filter approx. 15ms
3:Filter approx. 30ms
4:Filter approx. 60ms
1/1 0 Enabled /●●/●●6. 35. 1
H 0685
AM output gradient
characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1 Enabled /●●/●●6. 35. 3
H 0686 AM bias adjustment -10.0~100.0% 0.1/0.1 0.0 Enabled /●●/●●6. 35. 3
H 0688
MON1 voltage/current output
switching
0:Voltage -10~10V output
1:Voltage 0~10V output
2:Current 0~20mA output
1/1 1 Disabled /●●/●● *2
H 0689
MON1 output gradient
characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1 Enabled /●●/●● *2
H 0690 MON1 bias adjustment -10.0~100.0% 0.1/0.1 0.0 Enabled /●●/●● *2
H 0691
MON2 voltage/current output
switching
0:Voltage -10~10V output
1:Voltage 0~10V output
2:Current 0~20mA output
1/1 1 Disabled /●●/●● *2
H 0692
MON2 output gradient
characteristic
0:Negative inclination (downward slope)
1:Positive inclination (upward slope)
1/1 1 Enabled /●●/●● *2
H 0693 MON2 bias adjustment -10.0~100.0% 0.1/0.1 0.0 Enabled /●●/●● *2
This parameter moves to a fundamental parameter.
*1: For the adjustment range, see the table on page K-39.
*2: For details, refer to Instruction Manual (E6581341) specified in Section 6.41.