Toshiba Tosvert VF-AS1 Manual de usuario Pagina 241

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 312
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 240
K-3
E6581301
11
1. Basic parameter [3/4]
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
settin
g
unit
(
Panel/Communi
cation)
Default
settin
g
Write durin
g
runnin
g
Speed
control
Torq ue
control
PM
control
V/f Reference
VJT 0600
Motor overload protection
level 1
10~100% 1/1 100 Enabled /●●/●●5. 14
Settin
g
Motor t
y
pe
Overload
protection
OL stall
0 (protect) × (not stall)
1 (protect) (stall)
2 × (not protect) × (not stall)
3
Standard
Motor
× (not protect) (stall)
4 (protect) × (not stall)
5 (protect) (stall)
6 × (not protect) × (not stall)
QNO 0017
Motor overload protection
characteristic selection
7
VF Moto
r
× (not protect) (stall)
1/1 0 Enabled /
5. 14
●●5. 14
FURW 0701
Current/voltage unit
selection
0:%, 1:A (ampere)/V (volt) 1/1 0 Enabled /●●/●●5. 15
HOUN 0005
FM terminal meter
selection
0~64 *1 1/1 0 Enabled /●●/●●5. 16
HO 0006
FM terminal meter
adjustment
- 1/1 - Enabled /●●/●●5. 16
COUN 0670
AM terminal meter
selection
0~64 *1 1/1 2 Enabled /●●/●●5. 16
CO 0671
AM terminal meter
adjustment
- 1/1 - Enabled /●●/●●5. 16
EH 0300 PWM carrier frequenc
y
1.0~16.0kHz (1.0~8.0kHz) *2 0.1/0.1 *3 Enabled /●●/●●5. 17
WXU 0301
Auto-restart control
selection
0:Deselect
1:At auto-restart
2:ST ON/OFF switching
3:1+2
4:Starting
1/1 0 Disabled /●●/●●5. 18.1
WXE 0302
Regenerative power ride-
through control
0:Deselect
1:Power ride-through
2:Deceleration stop during power failure
3:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration signal)
4:Synchronized deceleration/acceleration (synchronized
acceleration/deceleration signal+power failure)
1/1 0 Disabled / -/- ●●5. 18. 2
RD 0304
Dynamic braking
selection
0:Deselect
1:Select (braking resistance overload detect)
2:Select (braking resistance overload not detect)
1/1 0 Disabled /●●/●●5. 19
RDT 0308
Dynamic braking
resistance
0.5~1000 0.1/0.1 *3 Disabled /●●/●●5. 19
RDER 0309
Allowable continuous
braking resistance
0.01~600.0kW 0.01/0.01 *3 Disabled /●●/●●5. 19
*1: For the adjustment range, see the table on page K-39. *2: For 200V-55/75kW models and 400V-90kW to 400V-280kW models, the carrier frequency is between 1.0 and 8.0kHz inclusive.
*3: Default values vary depending on the capacity. See the table of K-46.
Sensorless vector/vector with sensor (:Effective, -:Ineffective)
Vista de pagina 240
1 2 ... 236 237 238 239 240 241 242 243 244 245 246 ... 311 312

Comentarios a estos manuales

Sin comentarios