E6581301
F-35
6
*1
Stop position
control mode
Run command (F)
Preset speed 1 (S1)
Preset speed 2 (S2)
Stop position command signal (RR/S4)
Preset-s
p
eed o
p
eration fre
q
uenc
y
1
Preset speed operation frequency 2
0
Time [s]
Output frequency [Hz]
H
Positioning completion range
*1
Preset speed
operation frequency 2
If the stop position control command is entered during high-speed operation, a trip may occur because of
overcurrent or overvoltage. To avoid this, do not enter the stop position control command before the motor
enters into low-speed operation.
If a trip occurs because of overvoltage when stop position control is performed
If a trip due to overvoltage (OP2 or OP3) occurs when the motor is decelerated by stop position control, reduce the
proportional (P) gain with
H to prolong the deceleration time.
Note:The deceleration time setting (
FGE) has no effect during stop position control.
Proportional (P) gain (
H
)
During deceleration
Overvoltage trip
(
QR
or
QR
)
Time [s]
Output frequency [Hz]
Time [s]
Output frequency [Hz]
Acceleration
Deceleration
Acceleration