ut (Utility Parameters)
rnod
FnOd
Command/frequency mode selections
Related parameters
CflOd Command mode selection
FnOd Frequency setting mode selection
EflOd and FilDd select the terminal, panel and option inputs.
Enod , FilDd setting value
Function
0
Only RS232C input valid
1
Terminal input valid
d
Panel input valid
3
Communication option board input valid
4
Ali valid
Note)
RS232C input is
always valid.
★ The priority when set to 4 is as follows:
1. RS232C communication
2. Panel (select with PANEU/REMOTE key)
3. Terminal block (when selected by the user) Note)
4. Communication option board
5. Terminal block (normal)
Note) When 3 9 (panel/terminal mode selection) is allocated to a terminal with the input terminal selection
function.
When the switching signal is not input to the terminal, terminal block mode is selected.
The following three types of contact terminal inputs are always valid regardless of the
I LflDd and I F flDd I settings.
(Seep.55 C»-.5t f ft* I (*•• 0 ~ /0 )•)
Setting value
Function
E
RES (fault reset)
1
ST (gate ON/OFF)
ID
Emergency stop
E nPdl and I F nOd~\ can be changed while running, but the new settings wiil not become valid until
the motor has stopped once (O.OOHz). (Always stop once after changing j E HDdl or | F ilDd I.)