Gnxip
Hoist
Function
Trtle Adjustment range
Resolution Default
Re
marks
Dynamic braking selection (DBR)
Pb i
t
1
1
I
0: No DBR
1: With DBR, no OLr detection
2: With DBR and OLr detection
—
Dep«ndt
on Inverter
ratlrig
Gr.Pr
Overvoltage stall protection
GPSS !
1
1
0: ON
1: OFF
—
0 Gr.Pr
DC injection starting frequency
Other j DC injection current
than j DC injection time
0 !
dbP j
0-120
0.1/0.01 Hz 0.0
Gr.Pr
dbC I •
dbb j *
0-100%/A
0-10
1%/A
0.1 sec.
0
0.0
Forward/reverse DC injection priority
control
1
dbSL 1
0: OFF
1: ON
-
1
Gr.Pr
Emergency stop selection
[
£5bP j
1
.
............
j.. ..
0: Coast-stop
1; Decelerated stop
2: DC injection stop
—
0
Gr.Pr
1
2 I ESTOP DC injection time
Edbb j•
0—10 sec.
0.1 sec. 0.1
Motor overload protection level
bH^ ! j
10-100%/A
1%/A 100
Gr.Pr
OL reduction start-up frequency
CLP
0-30
0.1/0.01 Hz
30.0
Gr.Pr
OL selection
ril o
> 1
1
1
I
1
0: Standard
+1: Soft-stall ON
+2: OLMt trip OFF
—
0
Gr.Pr
Stall protection
SbC ! 1
1
1
0: ON
1: OFF
10-215%/A
1%/A
0
150
Gr.Pr
0 j Stall protection level (current
¡limit level adjustment)
ShL • I
Output short-circuit detection
selection (OCL)
c i
1
1
1
I
0: Standard
-M; High-speed motor use
+2: Position sensing
(during JOG)
0
Gr.Pr
Fault trip saving
1
1
1
0; Cleared when powered OFF
1: Data retained when powered
OFF
—
0
Gr.Pr
FM terminal function selection
cr^ci 1
r*i iDv- 1
1
t
1
1
0-13
Refer to the standard parameter
list for details.
0
Gr.AM
Frequency meter adjustment
PC
1
—
— —
Gr.AM
AM terminal function selection
RGSL i
1
1
I
0-13
Refer to the standard parameter
list for details.
3
Gr.AM
Ammeter adjustment
PC j
Gr.AM
Number of motor poles
GbP I
2, 4, 6, 8, 10, 12, 14, 16 2 4 Gr.Mt
Motor rated capacity
GbG j
0.1-75.0
0.1 kW (Ncte 1)
Gr.Mt
Motor type
Gbb 1
1
1
0: Toshiba standard motor
1: Toshiba VF motor
2; Other
—
0
Gr.Mt
2 1 Rated voltage
1 iCjlj • • 90-600 5V 200/400
j Rated frequency
GbP
0-400 2 Hz 60
»Rated RPM
\-
Gbi- j •
0-9999
1RPM
1710
1
¡Auto-tuning
1
1
Gbb<-» 1 *
1
1
0: Auto-tuning disabled
1: Auto-tuning enabled
-
0
Load moment of inertia
Gb. !H I
____
_______t -
0-3
-
1 Gr.Mt
(Note 1) Same as inverter capacity
-135