u r
P j (Panel Control Parameters)
PFb
r
Panel feedback control
This is used when Gr. F b feedback parameters are used.
* If no feedback control is selected with the C»~. Fb feedback control selection parameter j F bP I
feedback control will not occur even if panel feedback control ON ( PFbC = D) is selected.
Refer to the section on C r. F b for feedback control.
PrE5
Panel reset selection
The trip causes that can be reset when the inverter trips as a result of a failure or fault, etc., can be selected.
P r E 5 setting value
Function
D
All possible
1
Only OL can be reset
3
Only OL, 001, 0C2, and 0C3 can be reset
The trip cause must be removed before the inverter is reset, or the inverter will trip again.
OL indicates DL - in , DL - lib , and OLr . Resetting is not possible during the required cooling
time after tripping. The inverter can be reset, however, by turning the control power OFF.
Required cooling time under standard settings DL - In : Approx. 1 min.
DL - fib : Approx. 5 min.
DL r : Approx. 30 sec.
53 -