u r.
P (Protection Parameters)
dbF
d tj 5 DC injection braking settings ®
d b In
Related parameters
dbF
DC injection starting frequency
dbSL
d bC
DC injection current
db In
dbt
DC injection time
Forward/reverse DC injection priority control
Motor shaft stationary control
By setting the DC injection current, DC injection time, and DC injection starting frequency, the stopping precision
for positioning, etc. can be adjusted to match the load.
* DC injection braking is a function that forcibly stops the motor, so do not set dhC
than necessary, as the motor may overheat.
or
dbb higher
* The inverter’s overload protection sensitivity is increased during DC injection braking, so if dbC
is set
to approx. 90% or higher, the electronic thermal overload protection may activate depending on the
dbt setting.
(The overload protection will activate in approx. 3 sec. when \dbC is set to 100%.)
74 -