TOSHIBA
E6580516
High-Performance Inverter
Instruction Manual
TOSVERT VF-A5
200V
0.4
--55kW
400V
0.75
~75kW
NOTICE
1. Make sure that this Instruction Manual is delivered to the end
user of the inverter unit.
2. Read this manual before installing or operating the inverter
unit, and store it in a safe place for reference.
© 1994
Ver. no-'
TOSHIBA CORPORATION
Vista de pagina 0
1 2 3 4 5 6 ... 148 149

Indice de contenidos

Pagina 1 - TOSVERT VF-A5

TOSHIBAE6580516High-Performance Inverter Instruction ManualTOSVERT VF-A5200V0.4--55kW400V0.75~75kWNOTICE1. Make sure that this Instruction Manual is

Pagina 2 - Safety Precautions

3.3 Removal of the ROM Interface Window and Operation PaneiOperation panel( iV )ROM interface window(I) Press where the word PUSH is located. IThe to

Pagina 3

37kW'^-0l2 hole2-016 holeWARNINGFor safety reasons, unless making wiring connections, please leave this cover installed at all times.Never remove

Pagina 4 - Table of Contents

10. OptionsStandalone and installable options are available for this unit. Select according to your application.10.1 Standalone OptionsNameModelFunc

Pagina 5

10.2 Installable OptionsOption name Function and purposeModel Remarks (Note)cocCDQ.XQ>3Q.DO3Q.Ç12-bit Binary Input 12-bit binary inputVE5X-1526A A

Pagina 6

11. Error Displays and TroubleshootingInverter trip causes and remedies are shown in Table 11-1, and the causes and remedies of other

Pagina 7 - TRANSISTOR INVERTER

Table 11-1 Fault displays, details, and remediesDisplay Details Presumed causesRemediesReferencepageПРЭOvervoltage during constant speed run• The inpu

Pagina 8 - 2. installation Precautions

Table 11-1 Fault displays, details, and remediesDisplay Details Presumed causesRemediesReferencepage*UP 1Undervoltage trip (main circuit)• Input volt

Pagina 9 - 3.2 Removal of Cover

LOverload alarm Same asOL/nand DcntPOven/oltage alarmSame as dp i~DP3COvercurrent alarmSame as DC I~DC3HOverheat alarmSame as dhIf multiple alarms fro

Pagina 10 - Window and Operation Panei

11.2 Other Fault TroubleshootingPerform the following checks if other faults occur.The motor does not run.YesNoIs the LED display lit?Check the inp

Pagina 11 - 4. Operation Precautions

12. Maintenance and Inspection12.1 Preventive Maintenance and Periodic InspectionPreventive maintenance is required to operate this inverter in its

Pagina 12 - (Non-excited brake)

12.2 Component ReplacementThe inverter is composed of various electronic components including semiconductor elements.Periodic inspection of the f

Pagina 13

4. Operation PrecautionsObserve the following points when using the VF-A5 inverter4.1 Cautions Regarding MotorComparison with commercial power source

Pagina 14 - High-speed

13. storageObserve the following points when the inverter is not used immediately after purchase or when not used for a long period o

Pagina 15 - 5. Wiring Precautions

AppendixAppendix Table 1. Parameter listParameter groups ’ Cr. □1 KJUser parametersFFundamenta! parameters #1 (V/F, accel/decel etc.)Fundamental para

Pagina 16 - 5.3 Other Precautions

I IKJ(User Parameters)FunctionTiUeAdjustment rangeResolutionDefaultF*age(User-changed parameters)• Displays the parameters that differ from the standa

Pagina 17

0 (Fundamental Parameters #2)FunctionTitleAdjustment rangeFtesolutionDefault PagoMaximum voltage frequency #2———---------1----urLd ¡25~400 0.01/0.1 H

Pagina 18

(Special Control Parameters)Function . Title Adjustment rangeResolution Default PageStart-up frequencyF-5t1t0.0-10~ 0.1/0.01 Hz 0.164End frequencyF“£n

Pagina 19

St (Terminal Selection Parameters)FunctionTfUeAc^ustment rangeResolution DefaultPageInput terminal selection• 1 ¡h ;0: Standard terminal functions 1:

Pagina 20

FunctionTitleAdjustment rangeFtesolutionDefaultPageRR input specieU function selection1110. Standard 1: FH2: TACC/TDEC muitiplication fector 3. VB mul

Pagina 21 - 6. standard Connections

FunctionPreset speed selectionOther j Mode selection than 01j 1st speedj 1st speed run mode+•2 or j 2nd speed higher• 2nd speed run mode3or ¡3rd s

Pagina 22 - / 0 r 4 Note 4)

r~(Protection Parameters)Function Titte Adjustment rangeFtesolutionDefwHPageDynamic braking selection (DBR)Pb Ij0; No DBR1: With DBR, no OLr detection

Pagina 23 - I P b I in

Function TitfeAdjustment rangeResolution DefaultPageUndervoltage trip selectionUP5L I10: Trip disabled 1: Trip (during run)—080Undervoltage detection

Pagina 24 - 6.2 Terminal Functions

Braking during power off:Loads that generate a negative torque:Motors with brakes:The inverter will enter the coast-stop state when the power sourc

Pagina 25

Gi-Pb. (Pattern Run Parameters)FunctionTitle Adjustment rangeFtesolutionDetautt PagePattern run selectionPSEL—1-----10: OFF-082,83t_L - .1: ON1 Patter

Pagina 26

FunctionTitleAdjustment range ResolutionDefault1¡Speed #1 drive continuation mode 1 1 1 I 1 t 1i.._ ... ... ...

Pagina 27 - L surge

(Feedback Parameters)FunctionTiUeAdjustment range ResolutionDefaultPageFeedback control selectionFbP !tII-+ IIIIIII!II0; No feedback control1: PID con

Pagina 28

I ^ L« ^LjiT.c r”(Communication Parameters)FunctionTitle Adjustment rangeResolutionDefault PageRS232C baud rate b<“h0 i11110: 2400 baud 1: 4800 ba

Pagina 29

C ^JU t (Utility Parameters)FunctionTitleAdjustment rangeResolution DefaultPageIndustrial application parameters selectionRPL i 1 1 1 1 1 1 1i1j0; D

Pagina 30 - PB ^ PO ^2 ^3, ^2 % %

FunctionTrueAdjustment rangeResolutionDefault PageBlind function selectionfaL od0: Blind1; Selective unblinding—0501 j Fundamental parameters #21t-bLF

Pagina 31 - Main circuit terminal block

n(AM/FM Adjustment Parameters)FunctionTitle Adjustment range F)esolutionDefauRPageFM terminal function selection4FflSL !i1111I1I11i1111ti1jii110; Pre-

Pagina 32 - VUuUm V/T2 Wn^ PO PA PC PB

Appendix Table 2. List of trips • Trips (registered as past faults)oENo error (only during display of past faults)or- 1 1Overcurrent during accelerati

Pagina 33 - 7. Operation and Adjustment

Appendix Figure 1. Input terminai informationThe eleven input terminals correspond to the following bits. A group (input terminals 1 to 5)(Always I (O

Pagina 34 - 7.2 Basic Operation

Appendix Figure 3. Character codesCharacter codes (numbers)012 3 4 - 5 67 89—n11г3s&ot8 3-Character codes (letters)A a B b C cD d E eF fG gHh1 iJ

Pagina 35

Running with light loads:Power-factor improvement capacitors;Operating a large capacity motor with a light load using a small capacity (kVA) inverter

Pagina 36 - Parameter groups

Appendix Table 3. Standard default settings per inverter capacityInverter modelInvertertypeformdisplayVbhage boost .MaximumvottageDBR controlDBRresist

Pagina 37

Appendix Table 4. Industrial Application Parameters Industrial Application Parameters (Pump)When RP5. is set to { , . Z,<-P . CrD ! and Cr-Ub wil

Pagina 38 - 7.3 Operation Modes

Groupr-_r» I IPumpFunctionTitle Adjustment rangeResolutionDefaultRemarksRR input selectionnr- Jo—I-------11--1-------! •0: Standard 1: Adjustable—1 G

Pagina 39 - Status alarms

GroupFunctionTitleAdjustment rangeResolutionDefaltRemarksr~ 1PumpFeedback control selectionFbP !“T----111110: No feedback control1: PID control2: Spe

Pagina 40 - , Я f r 1 1 1 f

Industrial Application Parameters (Fan)When CriJt: RPL 's 5 • Cr-Li • Cr-F • GrQS C--iJt w'l' be available in settingmonitor mode, and

Pagina 41 - :r,,,,ii

Groupf-FanFunctionTitleAdjustment rangeFtesolutionDefaultRemarksRR input selectionrr in j. . j0: Standard 1: Adjustable-1Gr.SF1 {RR reference point #

Pagina 42

GroupFunctionTitleAdjustment rangeFtesolutionDefauKRemarksFanFeedback control selection1*2 ¡Feedback input signal ¡selection1)11111!_ .. ...

Pagina 43

industrial Application Parameters (Conveyor)When C^JDfc RPL is set to 3. , G--P , G^F3 . G--Pt . G^G!3 and GrJUt will beavailable in settings moni

Pagina 44 - “Decreasing"

Group r-„riDConveyorFunctionTitte Adjustment rangeResolution DefaultRemarks1 " ...Other ¡1st speed than 1Sr-C Î i. 1Lower limi

Pagina 45 - 7.3.4 JOG Run Mode

GroupZjConveyorFunctionTitleAdjustment range ResolutionDefauKRemarksi1-2 jAnti-hunting gain [ Lag time constantCR j »0.0~25.50.1s 0.00-255180PG input

Pagina 46 - 7.4 Operation Mode Selection

Use of multiple inverter units:Observe the following points when using multiple inverter units on the same power source line.High-speedAs

Pagina 47 - I P /7 0 d I in Cn.Ut I

Industrial Application Parameters (Hoist)When RPL. issettoH, Cr-JJ. . Gi-F? , Gr-GH and G<-Llb: will be availablein settings monitor mode, and th

Pagina 48 - —— Ut^ntTlu:

GnxipHoistFunctionTrtle Adjustment rangeResolution DefaultRemarksDynamic braking selection (DBR)Pb it11I0: No DBR1: With DBR, no OLr detection 2: Wit

Pagina 49 - 60Hz 80H z

The hoist application data initial settings that differ from standard settings are as follows.Group FunctionTitleDefaultRemarksC<“ShLjow-speed sig

Pagina 50

Industrial Application Parameters (Textiles)When C<-JLJfc RPL issettoS, Cr-U, , Cr-DS and Cr-iJfc will be available in settingsmonitor mode, and t

Pagina 51 - V/f settings

GroupFuncfion Title Adjustment rangeResolution DefaultRemarksTextilesEmergency stop selectionESfcP i 1 1... 1 . ...0: Coast-stop 1; Decelerated

Pagina 52 - V/f pattern ©

Industrial Application Parameters (Machine tools)When G<-Ub RPL is set to &, Gr-U , C/-F . Gr-GS and Gr-Gfc will be available

Pagina 53 - V/f pattern ®

GroupcTSsMachinetoolsFuncfionTitleAdjustment rangeResolutionDefaultRemarksDynamic braking selection (DBR)Pb ! 1 i10; No DBR1: With DBR, no OLr detec

Pagina 54 - Output frequency

GroupFunctionTitle Adjustment rangeResolution DefaultRemarksC^IDSMachinetoolsFM terminal function selectionFflSL i 1 1 110~13Refer to the standard p

Pagina 55 - 5 E H~ ■

Appendix Table 5. Changed settings memoDisplay the parameters that differ from the standard default settings with C <-.'J • make

Pagina 57 - Frequency setting signal

5. Wiring Precautions5.1 Connection to Main Circuit (Refer to page 11, Fig. 5.1.)Observe the following precautions when making connections to the inv

Pagina 58 - Acc/dec #1 and #2 selection

Ratings of connected meters:Rating of FL signal contacts:External use of control power:Open collector outputs:Frequency-settingpotentiometer:Connec

Pagina 59 - Panel reset selection

Note) A DC reactor (stand-alone type option) can be installed on 5.5kW and larger units. (Refer to the function of main circuit terminals PO and PA on

Pagina 60 - P b P R d E

Fig. 5.2 Wiring example using a magnetic contactorinstallation restrictions of secondary-side magnetic contactors(1) As a rule, if a magnetic c

Pagina 61 - Input terminal selections ©

Note) In this case, ensure that S4 is set to 'Emergency stop function", by setting | /h H [in 0 r. 5 h to ID.If the Th-Ry functions, the inv

Pagina 62 - Input terminal selections 0

Safety PrecautionsThis inverter is for driving a 3-phase motor, and must not be used for other applications.[I] Always observe the following items to

Pagina 63

Table 5.1: Examples of selecting equipment for wiringAppncabfemotormInverterNon-fuse breaker (MCC8)Magnetic contactor (MC)Overload relay Th-RyModelRat

Pagina 64 - DbL in Br.Pr

6. standard ConnectionsRefer to the operation selection expianation (7.4 Operation mode seiection, page 40), and parameter list (page 10

Pagina 65 - Time [S]

Example 3To set operating frequency with external signals, and forward/reverse run and decelerated stop with the panel.__________________3-p

Pagina 66

Example 5 When using built-in braking resistor (Note) Move PR1 wiring to PB1(For 3.7kW and smaller units)Setting: Set I Pbi in parameter group

Pagina 67 - I inCr-. F

6.2 Terminal FunctionsTable 6.2.1: Main circuit terminal functions for 3.7kW and smaller unitsMain circuit terminal functions for 3.7kW and smaller u

Pagina 68

Table 6.2.3. Control circuit terminal functionsControl circuit terminal functions are as shown below. The internal circuit diagrams for e

Pagina 69 - Run frequency control

Terminal symbolTerminal functionInternalcircuitdiagramST 3Q.C*—•0roc00CDJDCOeECOO)0Q.c00c3DThe standard setting is ‘run ready' with a short circ

Pagina 70 - End frequency

Fig. 6.2.1 Input/output internal circuits (1/2)SymbolInternal circuit diagramSymbolInternal circuit diagramE/UMS/litT/l><VaristorCapacitor4r1T

Pagina 71 - Jump frequencies

Fig. 6.2.1 Input/output internal circuits (2/2)SymbolInternal circuit diagramSymbolinternal circuit diagrame©©(DФ< CPU_a»v_ t. la TP2 < ®----

Pagina 72 - PWM carrier frequency

Terminal block coverFAR/Ll S/L2 T/L3U/Tl V/T2 W/T3'e©POWER SUPPLYMOTOR©EXT.RESISTORCONTROL R SLTPLYINTERNAL RESISTOR ON , OFFC/E FBRO SO( PBl)1 (

Pagina 73 - Preset speed operation ©

introductionThank you for purchasing the Toshiba High-Performance Inverter TOSVERT VF-A5'.The *VF-A5" inverter has many various functions bu

Pagina 74 - Preset speed operation @

5.5kW and larger units Removal ot RO and SO terminal shorting barsRemove the two terminal screws as shown below, and remove the shorting bar.Terminal

Pagina 75 - Frequency priority selections

Main circuit terminal block protective coversR/Ll 1 S/L2 1 T/L3U/Tl 1 V/T2 1 W/T3*"----POWER SUPPLY—------^—MOTOR-------IG/EMain circuit terminal

Pagina 76 - 5 tl P Jogging operation

10-M8 hex. screwp (5~pA,R/U S/L2 VUuUm V/T2 Wn^ PO PA PC PBPOWER SUPPLY MOTORNote) When using a braking resistor with 22kW and iarger units, the GTR7

Pagina 77 - Voltage between FV(CC

7. Operation and Adjustment7.1 Operation PanelThe operation panel (hereafter, panel) allows the inverter to be operated, and functions an

Pagina 78 - Output current

7.2 Basic OperationVerify the following items before starting operation.(1) Check that the wiring is correct.(Refer to Chapter 6, Standard connectio

Pagina 79 - (QL fit ) trip OFF

(2) Changing the frequency while runningStepOperation1)AENTERVThe frequency can be changed while running by pressing the UP key (A) or DOWN key (^. No

Pagina 80 - \dbC is set to 100%.)

Parameter groupsCr. U : User parametersGr.tr : Communication parametersC r. F ; Fundamental parameters #1C r.O / : Industrial application parameters(V

Pagina 81

The method for making setting changes is explained below using maximum voltage frequency ( C <-.F , , L >1) as an example.Key operationLED displ

Pagina 82

7.3 Operation ModesThis inverter unit has the following four operation and display modes.MONStatus monitor modeStandard monitor mode(Frequency settin

Pagina 83 - 0.01 -eookw

(3)Status alarmsAlarm characters and the frequency setting may be alternately displayed on the LED in standard monitor mode. The followi

Pagina 84 - ESEP E d b E

Table of Contents1. Acceptance Inspection and Precautions ... 12. Installation Precautions ...

Pagina 85 - FI r 5 t:

Trip occurrence example(Overvoltage trip occurrence during deceleration)Key operation Example displayExplanationDPSStandard monitor mode (Trip display

Pagina 86 - Trip function selections

This function monitors the various status items (frequency setting, output voltage, current, terminal7.3.2 Status Monitor Modeinformation,

Pagina 87 - Fault trip saving

Note 1) When \ d / 5 <- ] in C <-.F (reverse run disable selection) is set to / , the display will always be: : F r- -

Pagina 88 - P 5 E L. PEP Pattern run ©

(2) Settings monitor mode adjustment function (Parameter group C r.Rfl )This function is used to adjust the scale when an analog meter is

Pagina 89 - PSEL PEP

(3) Setting value alarm displayWhen a setting value and one of the following alarms are alternately displayed on the LED, a setting

Pagina 90 - Panel operation permission

7.3.4 JOG Run ModeThis mode is used to run the inverter at low speeds, and especially allows short-time runs (inching) to be done e

Pagina 91

7.4 Operation Mode SelectionThe methods for operation and adjustment from the operation panei, validating/invalidating operating commands

Pagina 92 - (Utility Parameters)

7.4.4 Parameter Setting Function f I P /7 0 d I in Cn.Ut IParameters can be set in the standard mode, but alternatively, the panel operati

Pagina 93 - Lit (Utility Parameters)

7.4.5 Standard Parameter Value Reset Function [ | fc H P | in Ci-.Ub ]All parameter values can be changed to standard settings at one time by setting

Pagina 94

OHz 50HzOutput frequency60HzOHz60Hz 80H zOutput frequencyNote 2) When Note 3)fc y PFig. 7.5 Standard Setting Value= 3 is selected, all parameters o

Pagina 95 - Meter adjustment parameters

2. Cr.Pn Acc/dec #1 and #2 selection ... 52Panel feedback control ...

Pagina 96 - 9. Device Specifications

(Note)ESfcP in Cr.Pf- settings: DICoast-stop Decelerated stopEmergency DC injection braking stopIf E is selected, also set the DC injection currentdb

Pagina 97 - General specifications

8. Parameter Explanationsr- ^LJ f~ , I (Fundamental Parameters #1)UL IUL5LUL U IV/f settings(Output voltage and frequency ratio setting)Related para

Pagina 98

r~ , F~ (Fundamental Parameters #1)PbV/f pattern ©Related parametersV/f patternPt,b I,L IVoltage boostMaximum voltage frequencyCr-. nt nt.Pnt£nt.tnt.L

Pagina 99 - 2>ATheW

F(Fundamental Parameters #1)PtV/f pattern ®Parameter setting process when | Pt I is set to 3 Cn.FCpF]v/f pattern1: V/f control (using co

Pagina 100 - ________

Or. F(Fundamental Parameters #1)О Г 1 ri L L- 1dE-L IAcceleration/deceleration time settingsЯСС 1Acceleration time #1 Cr. F3ЯССЗdEC 1Deceleration time

Pagina 101 - 10. Options

ür. F(Fundamental Parameters #1)rs C Lj- Acc/Dec patterns,5LL5 E H~ Acc/Dec pattern adjustment, Low/HighRelated parametersSCu 1Acc/Dec pattern #1SCLA

Pagina 102 - 10.2 Installable Options

u r,LJ b(Utility Parameters)b L n d Blind function selectionRelated parametersbLnd Blind function selectionbL Fg I ~ I bL /lb Group blind selectionsIt

Pagina 103 - 1 , PDFF, (TOFF •

и г.F(Fundamental Parameters #1)( Г I и L-Upper limit/lower limit frequenciesRelated parametersUpper limit frequencyULLLLower limit frequencyThe upper

Pagina 104 - 1 oLEL l •

[j f- , P n (Panel Control Parameters)P cd P Acc/dec #1 and #2 selectionRelated parametersRd3 Acc/dec #1 and #2 selectionC r.F 3 Rd3F Acc/dec #1 and

Pagina 105

u rP j (Panel Control Parameters)PFbrPanel feedback controlThis is used when Gr. F b feedback parameters are used.* If no feedback control is selected

Pagina 106

8. Cr.ufc Panel operation permission ... 84Industrial application parameters selection ...

Pagina 107 - O.D displayed?

r ^ u r •n (Panel Control Parameters)P b P R d EFundamental parameter switchingRelated parametersPbP Fundamental parameterRdPAcc/dec #1 and #2 selec

Pagina 108

u r5 Izi Selection Parameters)ItInput terminal selections ©to It IDRelated parametersItItDIt I IIt 10Input terminal selection Input terminal function

Pagina 109 - 12.2 Component Replacement

^ ^ (Terminal Selection Parameters)lb-Input terminal selections 0IbOlb ID* The relationship between the settings of C flDd and FflOd in C r.U t and t

Pagina 110 - 14. Warranty

u r.5 tz 0*6'’'^'^^’ Selection Parameters)ObO0 t3____Output terminal selections ®The functions for the output terminals RCH ( 0 fc 0 ).

Pagina 111 - Appendix

u r.^ (Terminal Selection Parameters)Oh 3 J Output terminal selections @Open collector output detection level•ON* : open collector transistor ON

Pagina 112 - (Fundamental Parameters #1)

u r.5 tz {Terminal Selection Parameters)LFbr EHH r E HL r E HLow speed, acceleration/deceleration complete, speed reach output signalsLFLow-Speed sign

Pagina 113 - (Panel Control Parameters)

LJ r .5(Terminal Selection Parameters)IbFI b 5 Fu h 0 d0 b 0 hInput/output terminai response time selectionsRelated parametersIbFIbSFIblFDbOdDb3dOb

Pagina 114 - (Special Control Parameters)

» —и г.5 ¿Z Selection Parameters)ггу^ги ииFCHCI Commercial power/lNV switchingRelated parametersCommercial/inverter switching output Commerciai/inver

Pagina 115 - \ Input terminal 10 (S7)

U r.^ (Terminal Selection Parameters)[J tl F P Output terminal pulse frequency selectionSelects the No. of pulses in proportion to the output frequenc

Pagina 116

u r.^ (Special Control Parameters)FrunF 5 Run frequency controlRelated parametersFr un Run frequency FHy Sj frequency hysteresisThe inverter run/stop

Pagina 117 -

1. Acceptance Inspection and Precautions(1) Confirm that the unit has not been damaged during shipment.(2) Confirm that the model noted on the ratin

Pagina 118 - (Protection Parameters)

Cr-. Sir—(Special Control Parameters)F - 5 bStart-up frequencyF - E nEnd frequencyRelated parametersF - 5t Start-up frequencyF - En End frequencyThese

Pagina 119 - 1 Rated RPM

r.^ (Special Control Parameters)FJ.nJump frequenciesRelated parameters F J.n Jump frequency selectionFJ /FJ3bFJ 1~bFJ3Jump frequencies Jump bandsTo a

Pagina 120 - (Pattern Run Parameters)

u r.^ f“ (Special Control Parameters)CFPWM carrier frequencyThe motor's resonant acoustic noise can be changed by changing the PWM ca

Pagina 121 - \ Speed #5 drive time

Or. OF (Frequency Setting Parameters)5 r.n5 r. n I Preset speed operation ©Related parameters5 r-.nPreset speed selection5r0 15r-15Sr-.nMode selection

Pagina 122 - (Feedback Parameters)

Or. OF(Frequency Setting Parameters)5 r.nOr.nPreset speed operation @Example of 7-speed runOutput frequencyS3CCThe above example assumes that the foll

Pagina 123 - LjiT.c r”

u r.^ ^ (Frequency Setting Parameters)FTRLEFrequency priority selectionsRelated parametersFC f FEE Frequency priority selections/r»F Analog input filt

Pagina 124 - C ^JU t (Utility Parameters)

Or^ p- (Frequency Setting Parameters)OOPlJ 5 tl P Jogging operationRelated parametersJog run frequencyJDOJ5bP Jog stop controlA jog run can be st

Pagina 125

0 r.5F(Frequency Setting Parameters)r rInFrequency setting input signal characteristicsRelated parametersr r inRR input selectionF-P 1p 1RR reference

Pagina 126 - (AM/FM Adjustment Parameters)

u r.(Protection Parameters)Related parameterstHr /Motor overload protection levelDLLDLFOL reduction start-up frequencyMotor 150% overload time limitTh

Pagina 127

u r.r(Protection Parameters)01 nL- I iElectronic thermal protection @DLOOL selectionStL /StC 1Stall protectionThe OL selection parameter| QL H can be

Pagina 128

2. installation PrecautionsThis inverter is an electronic control unit. Take special care concerning the installation environment.Confirm that the

Pagina 129

u r.P (Protection Parameters)dbFd tj 5 DC injection braking settings ®d b InRelated parametersdbFDC injection starting frequencydbSLd bCDC injection c

Pagina 130

DC injection braking wiil start when the inverter stop command is issued and the output frequency is less thanTime [S]©When©WhenWhend bFdbFdbFF - E n

Pagina 131

Or. Pr(Protection Parameters)d tj F db5LDC injection braking settings ©d h InI db /«->1 Motor shaft stationary controlThis function is effective

Pagina 132 - +2: OLMt trip OFF

u r.(Protection Parameters)P bfp tj nPbCPOP55Dynamic braking operationRelated parametersPbDynamic braking selectionPbCPPbrDBR resistor valueDP5SDBR ca

Pagina 133 - F-P'-t

Or. P r (Protection Parameters)ESEP E d b EEmergency stopRelated parameters£ 51 p I Emergency stop selectionEmergency stop is not allocated to a term

Pagina 134 - 'b 3

LJ rP(Protection Parameters)I I U U^ fLJ LJ L-Regeneration power ride-through controlRelated parametersUuC I Regeneration power ride-through control

Pagina 135 - +1: Soft-stall ON

u rP I— (Protection Parameters)5t ClUP5L Trip function selections1 1 L_ L-PDt 5Lu tzLb r C LRelated parameters5LC 1Stall protectionStL 1UP5LUndervolta

Pagina 136

^ P (Protection Parameters)u ^ ILZ Lmm ImFault trip savingDependent upon the setting of this parameter, trip causes can be displayed after power is c

Pagina 137 - 1 Input terminal 10 (S7)

LJ r .Pt(Pattem Run Parameters)P 5 E L. PEP Pattern run ©Related parametersPattern run mode Pattern group number of cycles Speed drive timesInput term

Pagina 138 - PbP ! i

U r.P (Pattern Run Parameters)PSEL PEPPattern run @5 L n set to 4Ptnptn = 0Time [S]Run signai_r5 L n set to 5Time [S]* Allocate the pattern run step t

Pagina 139 - 1 Parameters (Conveyor)

3. External View and Component Names3.1 Component Explanation (I)0 Cooling air exhaust port® Mounting hole (4 holes)® Mounting bracket ® Operating

Pagina 140 - F-P8 1 «

u r. u"b(Utility Parameters)PnOd PR55 Panel operation permissionRelated parametersPnOd Panel operation mode selectionPR55 Pass numberVarious leve

Pagina 141

U r. U b(Utility Parameters)R PIIndustrial application parameters selectionThis parameter is used to configure various industrial application paramete

Pagina 142

r"u r.ut (Utility Parameters)rnodFnOdCommand/frequency mode selectionsRelated parametersCflOd Command mode selectionFnOd Frequency setting mode s

Pagina 143 - 1 RR reference point #2

r~LJLit (Utility Parameters)non I I i r? D n W Status monitor display selectionsThe 4 programmable status monitor items can be selected from the follo

Pagina 144 - See >

LJ r .Lit (Utility Parameters)d 5 P ^ Units settingsRelated parametersdSPBFrequency units multiplication factordSPCdSPFFrequency display resolutiondSP

Pagina 145 - \ terminal)

U r.RH(AM/FM Adjustment Parameters)FRSL.RR5LFRHRMeter adjustment parametersRelated parametersFP5LFM terminal function selectionRP5LFPFrequency meter a

Pagina 146 - ' 1

9. Device Specifications9.1 Model and Standard Specifications200V SeriesttemStandard specificationsVoltage class200V classApplicable motor (kW) 0.40

Pagina 147 - 1 Parameters (Machine tools)

General specificationsControl method Sinusoidal PWM controlOutput voltage regulationMan circuit voltage feedback control. (Automatic regulation, “fixe

Pagina 148 - I..J ;..j

cJOoa.Protective functionsStall prevention, current limit, overcurrent, overvoltage, load-side short circuit, load-side ground fault, undervoltage, mo

Pagina 149 - TOSHIBA CORPORATION

9.2 External Dimensions3.7kW and smalierModel VFA5-2004-2037 - VFA5-4007-4037t # g hewVi1\ rlMiB□O0 Airflow directionQDimensions (mm)W H DA B140 280