Table 5.1: Examples of selecting equipment for wiring
Appncabfe
motor
m
Inverter
Non-fuse breaker
(MCC8)
Magnetic
contactor (MC)
Overload relay
Th-Ry
Model
Rated
current
(A)
Toshiba
model
Rated
current
(A)
Toshiba
model
(Note 1)
cunvnt value
_ w
{Reference
vfeue]
Toshiba
model
0.4
-2004P
5
SS30
12
C12A 2.3
T11A
0.75
-2007P 10
SS30
12 C12A
4.2
T11A
1.5
-2015P 15
SS30
12 C12A
6.6
T11A
2.2
-2022P
20 SS30
12 C12A 9.3
Til A
3.7
-2037P 30
SS30 18
C20A 15
T20A
5.5 -2055P
50
ESSO
35 C35A
22
T35A
7.5 -2075P
60
EH100
50 C50A 28
T35A
11
-211 OP
100
EH100
65 C65A 43
T65A
15 -2150P
125 EH225
80
C80A
57
T65A
18.5 -2185P
125
EH225
93 C100A 70
T80A
22 -2220P
150
EH225 93
C100A 85
T125A
30 -2300P 200
EH225
180 C180A 108
T125A
37
-2370P
225
EH225 180
C180A
138
T150A
45 -2450P
250
EH400
220 C220A 162
T180A
55 -2550P
250
EH400 220
C220A
198
T220A
75 -2750P
500 SH600
300 C300A
3.6
T400A
0.75
-4007P
5
SS30
9 C12A 2.3
Til A
1.5 -4015P 10
SS30 9
C12A 3.6
T11A
2.2
-4022P 10
SS30
9 C12A 5.0
Til A
3.7
-4037P 15
SS30 9
C12A
8
T11A
5.5
-4055P
30
SS30
17
C20A
11
T20A
7.5 -4075P
30 SS30
17
C25A 15
T20A
11
-4110P
50
ESSO 33 C35A
22
T35A
15 -4150P 60
EH100 48
C50A 28
T35A
18.5
-4185P 75
EH100 50
C50A 35
T35A
22
-4220P
100 EH100
50 C50A 43
T65A
30
-4300P
125
EH225 80 C80A
57
T65A
37
-4370P
125
EH225 93
C100A
70
T80A
45 -4450P 150
EH225 180 C180A 85
T125A
55
-4550P
175 EH225
180 C180A 108
T125A
75
-4750P 225
EH225
220 C220A
138
T150A
Voltage
dass
Surge killer
Model
(Note^
Wire size
Main
ciicuit
(mm^
(Notes)
Control
dfcuit
(mm^
(Note 4)
Dynamic
braking
(mm®)
200V
class
2.0
Toshiba
model SS-2
or
Marcon
Bectronics
RFM2E224KD
2.0
2.0
2.0
0.75 or
larger
3.5
14
5.5
14
22
8.0
38
38
22
60
100
100
60
100
100x2
400V
class
2.0
Model SS-2
or
Marcon
Bectronics
RFM2H104KD
(400V system)
(Note 6)
2.0
2.0
2.0
0.75 or
larger
3.5
5.5
2.0
3.5
14
22
8.0
38
38
38
22
60
100
(Note 1) When selecting a magnetic contactor (MC) with 2a auxiliary contacts and using the auxiliary contacts for the control circuit,
parallel the 2a contacts to improve contact reliability.
(Note 2) Install a surge killer on the magnetic contactor or relay exciting coil.
(Note 3) The wire sizes for the input side R, S, T and output side U, V, W are shown. These sizes apply only when the wiring length is
less than 30m. Increase the wire sizes when the length exceeds 30m.
(Note 4) Use shielded wire.
(Note ^ Use a wire size 3.5mm® or more for the grounding wire.
(Note 6) 200V system: type SS-2 or Marcon Bectronics RFM2E224KD
- 14 -