(3)
Status alarms
Alarm characters and the frequency setting may be alternately displayed on the LED in standard
monitor mode. The following four types of characters may be displayed.
C .... When current exceeding the overcurrent stall level flows.
P .... When voltage exceeding the overvoltage stall level is generated.
L •— When 50% or more of the overload trip value is reached.
H .... When the temperature reaches the overheat protection alarm setting level.
Several alarms may also be displayed simultaneously. (’ lC’ ” PC’ ’ LPC’ )
The alarms will automatically go out when the alarm condition is removed.
(4) Trip information
The standard monitor mode trip display will be entered immediately when a trip occurs.
Display
Explanation
OC ;
Overcurrent during acceleration
DCS
Overcurrent during deceleration
DCS
Overcurrent during constant-speed run
DC IP
DC section overcurrent during acceieration
DCSP
DC section overcurrent during deceleration
DC3P
DC section overcurrent during constant speed run
DCL
Load-end short circuit (output terminal check) trip during start-up
OCR /
U-phase short circuit
DCRS
V-phase short circuit
DCP3
W-phase short circuit
DP 1
Overvoltage during acceleration
DPS Overvoitage during deceleration
DP3
Overvoltage during constant-speed run
DL In
Inverter overload trip
Dtnt Motor overload trip
DCr
Dynamic braking resistor overcurrent trip
DLr
Dynamic braking resistor overload trip
DH Overheat trip
E
Emergency stop
EBP 1
EEPROM fault (write error)
EEPS
Initial read fault
ErrS
RAM fault
E r 3
ROM fault
E t~ r R
CPU error trip
E r r 5
Communication run command interruption error
Er-rE
Gate array fault
Er-rl Output current detector fault
ErrB
Option PCS fault trip
UC
Low-current operating condition trip
UP 1
Undervoltage trip (main circuit)
Oh
Overtorque trip
EF loiEFS
Earth-fauit trip
E t n Auto-tuning error
Et UP
Inverter typeform error (Special error, refer to page 42.)
n E r r
No error (Refer to past trip display on page 35.)
The inverter status at the time of the saved trips (trips that previously occurred) can also be read.
(Refer to Status monitor mode on page 35.)
-33 -