4200FA-XT1 May, 2008 1 TOSHIBA International Corp GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 15 kVA
4200FA-XT1 May, 2008 107.0 SERVICE AND WARRANTY A. Reliability System mission reliability 240,000** hours and including bypass MTBF (Mean-Ti
4200FA-XT1 May, 2008 2(15 kVA XT) 1.0 SCOPE 1.1 System This specification describes a continuous duty, three-phase, on-line, solid-state u
4200FA-XT1 May, 2008 3H. Input / Output EMI / RFI Filters 2.3 System Operation The UPS shall operate as an on-line, fully automatic
4200FA-XT1 May, 2008 4protection against spikes, common/normal mode noise, load steps and frequency shifts (without battery back-up capability
4200FA-XT1 May, 2008 5 +/- 3% (loss or return of input power) +/- 8% (bypass to inverter) 13) Transient Voltage Recovery 50ms m
4200FA-XT1 May, 2008 6 4.0 FUNCTIONAL DESCRIPTION A. Converter / Charger / DC Chopper DESCRIPTION - The converter/charger shall consist of
4200FA-XT1 May, 2008 7 2) OVERCURRENT PROTECTION - The output circuitry shall be equipped with a Hall Effect Current Transformer to detect a
4200FA-XT1 May, 2008 83) SYSTEM METERING - The UPS shall be provided with a single read- out display which displays, upon request, the followi
4200FA-XT1 May, 2008 9 B. Cable Entry The UPS shall be provided with cable entry from the bottom of the UPS enclosure. C. Ventilation and